Voltage Drop & Wire Size

Percent voltage drop from amps, one-way length, gauge, and material, plus the gauge that meets your 3% target, the maximum length at that target, and the watts you lose.

3% on the branch circuit and 5% total from the transformer is the design target most engineers use. The branch is half of it, which is what makes long runs expensive.

—Voltage drop (percent)
—Volts lost in the run
—Watts wasted in the conductor
—Gauge that meets your target
—Max length for your gauge at target
—Cost of upsizing vs your gauge
How the math works
  • Formula: voltage drop = (2 × K × amps × one-way feet) ÷ circular mils for single phase, with 1.732 replacing the 2 for three phase. K is 12.9 for copper and 21.2 for aluminum at operating temperature.
  • Circular mils: 14 = 4,170, 12 = 6,530, 10 = 10,380, 8 = 16,510, 6 = 26,240, 4 = 41,740, 2 = 66,360, 1/0 = 105,600, 4/0 = 211,600. Aluminum is 1.64x the resistance of copper at the same size, which is the 3-size-upsizing rule.
  • Targets: 3% branch-circuit drop, 5% total from the service transformer, 10% cumulative on a feeder + branch chain. The NEC gives these as FINE notes (9005.5), not as a mandatory rule: a conductor that meets ampacity and protection is code-legal at 6% drop.
  • Wasted power: drop × amps = watts lost as heat in the conductor. A 20 A branch at 5.4 V drop burns 108 W continuously, which is about 950 kWh a year on a 24/7 load.
  • Max length: length = circular mils × target% ÷ 100 × volts ÷ (2K). At 3% and 20 A on 230 V, 12 AWG tops out at 75 ft one-way.
Resistance-based voltage drop at conductor operating temperature (75°C), which is the conservative number for sizing. Motor starting inrush, non-linear loads with neutral harmonic current, AC impedance on steel conduit (which raises the drop 10 to 20% above the DC number), and long DC PV strings are outside this model. Voltage drop is a performance target, not a code requirement.

What is the code-allowed voltage drop?

The NEC recommends 3% for a branch circuit and 5% total for feeder plus branch, and calls them Fine (informative) notes, not mandatory. A circuit wired to ampacity and protection rules is legal at 6%, and most utilities and engineers push for 3% on branch, 10% cumulative.

How far can I run 10 gauge at 20 amps?

At 3% on a 230 V single-phase load: 10 AWG (10,380 cmil) tops out at 120 ft one-way. At 120 V, 10 AWG takes you 63 ft at 3% and 104 ft at 5%. Distance halves when voltage halves.

Do I size for voltage drop before ampacity?

Ampacity and overcurrent protection first: that is the code. Voltage drop is the performance check that tells you the wire is code-legal and the motor gets 208 V instead of 230. When the drop fails, you upsize the conductor, not the breaker.